Distribution Center - Cleveland, OH

energy efficient heater in large warehouse









Cleveland Building Layout











Click on Diagram for Close-Up


Cleveland Temperature Graph














Click on Graph for Close-Up

BUILDING DETAILS:
Size: 121,000 sq. ft. x 27 ft. high
Construction: R-20 Roof
R-11 Walls
OPERATING CONDITIONS:
Operating Hours: 24 hrs/day 5 days/wk
Design Temperature: 65°F @ 0°F
Thermostat Settings: 63°F weekdays
60°F weekends
Heating System:
  • (2) Cambridge heaters
  • Thru-Wall Mounting
  • 14,000 total CFM


RESULTS:
(5) Temperature loggers placed throughout the distribution center confirm that only (2) wall mounted Cambridge heaters maintain an even 63°F temperature during weekdays and 60°F setback on weekends during the winter. Temperature variances within the building were only 2°F wall-to-wall and 4°F floor-to-ceiling despite outdoor temperatures fluctuating from 18°F to 59°F. Actual gas consumption was only $0.08/sq. ft. for the heating season (Gas@ $0.50/therm).